REPORT ON TESTS OF PHYSICAL AND FIRE EXTINGUISHING PROPERTIES
OF FIRE EXTINGUISHING POWDER “IMPULSE-STORM”
 
 
 
 
No 16-IS
 
Date November 12, 2006
 
 
Tested material characteristic
 
The object of the tests is a fire extinguishing powder “Impulse Storm Powder” ISP. The fire extinguishing powder is a mono-containing material and represents a fine-ground mineral of natural origin. The mechanism of fire extinguishing action of the powder is in inhibiting the reaction of burning by means of binding active centers of chain reactions occurring in the flame.
Powder having dispersion of not less than 40 mkm was provided for the tests.
 
 
Methods for conducting tests
           
            The tests of the fire extinguishing powder “Impulse-Storm” are conducted in accordance with the Norms of Fire Safety of Russia No. 170-98 “Fire extinguishing powders of general purpose. General technical requirements. Methods of tests”.
The following technical characteristics are determined:
-          apparent density of non-compacted powder;
-          apparent density of compacted powder;
-          determining dimension of powder particles;
-          determining capacity for extinguishing a model fire center of A class;
-          determining capacity for extinguishing a model fire center of B class;
 
 
 
 
 
 
Devices and equipment
 
Table 1 – Testing equipment, materials
 

Name of TE
Main technical characteristics
Glass measuring cylinder with plug stopper

Diameter 35 ± 5 mm, capacity 250 cm3

Vibration stand

Vibration with frequency of 100 Gz,

vibration acceleration from 50 to 150 m/sec2

Stop watch “Agate”

 

Metal sieves. Soft brush.

Nets No. 1, No. 01, No. 005 according to standard

GOST 6613 with a lid and a tray

Gasoline À-76

 

Wooden bars

Section 39 ± 1mm, length 500 mm

Fire extinguishing powder “Impulse-Storm”

Selected sample 40 kg

 
 
Conditions for conducting laboratory tests:
 
- temperature +20°Ñ;  
- atmosphere pressure 101 kPa;  
- relative humidity 85%;
 
 Conditions for conducting firing tests: 
 
- temperature +20Ñ;
- atmosphere pressure 101 kPa;
- relative humidity 85%;
- wind speed 0,5 – 1,0 m/sec.

 

 
Results of conducting tests
 
            Table 2 – Determining apparent density of non-compacted powder
           

No.
Mass of powder sample, g
Volume of powder sample, cm3
Apparent density, kg/m3
Sample No. 1
100
121,9
820
Sample No. 2
100
121,6
822
Sample No. 3
100
121,8
821

 
            Table 3 – Determining apparent density of compacted powder
 

No.
Mass of powder sample, g
Volume of powder sample, cm3
Apparent density, kg/m3
Sample No. 1
100
95,2
1050
Sample No. 2
100
92,5
1080
Sample No. 3
100
93,
1070

 
 
            Table 4 – Tests on determining dimension of powder particles
 

No.
Mass of powder sample, g
Mass of powder on net No.1,
g
Mass of powder on net No.0,1,
g
Mass
of
powder on net No.0,05,
G
Contents of
residuum on net No.1,
%
Contents of
residuum on net No.0,1,
%
Contents of
residuum on net No.0,05,
%
Summary powder residuum on nets,
%
Sample No. 1
20
0
0,42
1,3
0
2,1
6,5
8,6
Sample No. 2
20
0
0,3
1,28
0
1,5
6,4
7,9
Sample No. 3
20
0
0,34
1,32
0
1,7
6,6
8,3

 
Table 5 – Tests on determining capacity for extinguishing a model fire center of A class
 

 
 
No.
Model fire center rank
Fact of
extinguishing a fire center
Mass of
powder for extinguishing a model fire center, kg
Time of
extinguishing a fire center, sec
Intensity of fire
extinguishing powder
supply,
kg/(sec.m2)
Specific
consumption of fire
extinguishing powder,
kg/m2
1
Fire center extinguished
7,52
34
0,221
1,6
2
Fire center extinguished
7,76
36
0,215
1,65
3
Fire center extinguished
7,66
32
0,239
1,63

 
Table 6 – Tests on determining capacity for extinguishing a model fire center of A class
 

 
 
No.
Model fire center rank
Fact of
extinguishing a fire center
Mass of
powder for extinguishing a model fire center, kg
Time of
extinguishing a fire center, sec
Intensity of fire
extinguishing powder
supply,
kg/(sec.m2)
Specific
consumption of fire
extinguishing powder,
kg/m2
1
55Â
Fire center extinguished
2,72
16
0,17
1,53
2
55Â
Fire center extinguished
2,77
17
0,18
1,56
3
55Â
Fire center extinguished
2,81
19
0,15
1,58

 
         

Deputy Chief of Department
for Fire Research and Tests
 
 
V.A.Chizhov
Junior Research Officer of Department
for Securing Fire Safety of Objects
in Low Temperature Conditions
 
 
V.A.Negin
 
Senior Engineer of Department
for Fire Research and Tests
 
 
A.V.Antonov

 
NEWS
15.06.2010 - Upgraded system UIS-48S with automatic infrared aiming was tested and certified
15.03.2010 - Visit of the New Impulse Technologies delegation and delegation of the Ministry of emergency situation of Russia to Brazil
10.12.2009 - On December 1st, 2009, on special order of company Petrobras,
28.11.2008 - An impulse fire extinguishing system was tested on Pelyatka gas-condensate field.
03.07.2008 - A public presentation of the newest fire extinguishing technology “Double Storm” took place.
Archive of news
CONTACTS
The impulse fire installation “Impulse Storm” is destined for extinguishing large fires on gas and oil fields, atomic and thermoelectric power stations without cutting off voltage, and in ammunition depots. The speed of fire powder supply – 300 kg/sec…

Details>>
Jet gas and water extinguishing installation JFR-250. Speed of gas and water mixture delivery – 200 kg/sec. Distance of delivery – up to 70 m. Extinguishing sector - 90. Possibility of remote control.

Details>>
«Multifunctional impulse powder fire extinguisher «IMPULSE STORM» Clause 7. 3 of the Official Report on certification tests The Siberian Affiliate of the All-Russian Scientific and Research Institute for Fire Defense, Russia, No. 10-02 of July 20, 2002 “The quantity of leakage current according to powder air suspension in combination with powder supply means which excludes contact of the operator with the fire center...
Details>>
  Copyright © 2003-2004 New Impulse Technologies LLC Hosting & Design VLine Telecom